PROTECTION

Читайте также:
  1. Environmental protection in Ukraine
  2. Soil protection and their rational use

OVERLOAD PROTECTION:

UPS output transform from inverter to bybass mode when load is 105% of rated load(VA, or wattage) is going on running on for 10 seconds.When the load is higher than 130% of rated load,the UPS transfers to bybass immediately.

BATTERY VOLTAGE ABNORMAL PROTECTION:

When battery voltage is unnormal on battery-under or battery-higher level,then the panel is indicated fault and shut down.

INVERTR OUTPUT ABNORMAL PROTECTION:

The pannel is indicated the fault when inverter abnormal.

OVER TEMPERATURE PROTECTION:

CNTL dectects the temperatue of PSDR heatsink by the thermal switches are electrically connected to the CPU.When over temperature,the pannel will indicated the fault condition.

 

2.3.2 INTERFACE SINGAL TRANSMITTING: To show the UPS status on the computer

via cmmunication interface soft.

 

2.3.3 VOLTAGE REGULATION & CONTROL UNIT:Definitely, brain of UPS is CNTL.It provides control singal to switching elements,regulates UPS output to supply stable SINE wave to load.

 

 

PANEL LED AND BUZZER INDICATION

PANEL LED INDICATE

When UPS occurs as flowing:

BUZZER and LED INDICATE

When UPS occurs as flowing:

Low battery voltage: beeping every seconds

 

e. Replace battery: The load and battery LED is flashing alternately and beeping every second.

 

c. Back up mode: beeping every four seconds

 

d. Silence:Push ’turn on ‘ key to silence your ups that buzzer to stop beeping.

 

e. Fault: continuous beeping

 

f. Over load is 105~130%: all LED are lighting on and beeping every second

 

note 1:When UPS occurs fault and AC line normal,then UPS stop output and AC line input realy switch.Until pushing ‘off’ button,UPS turn off lastly.

ALIGNMENTS

Definition of variable resistors on PSDR

VR definition
VR1 Accurate 5V±0.01% renference voltage adjustment
VR2 Battery voltage adjustment

Adjustment

PCB MEASURE MEASURE POINT MEASURE AND ADJUSTMENT SEQUENCE EXPECTED RESULT    
PSDR   DC(+)BUS P16(+) O/P_N Connect DVM (DC) to measure points and connect I/P ac power cord,then turn on switch. ULT-700 +380VDC±10V +190VDC±10VDC ULT-1500  
DC(-)BUS P16(-)BUS O/P_N Connect DVM (DC) to measure points and connect I/P ac power cord.then turn on the switch.    
CHARGER P15(+) P15(-) 1.Disconnect Bat(+),Bat(-) 2.Connect DVM(DC) to measure points and connect I/P AC power cord, 3.Adjust VR2 to obtain the expected result. 4.Reconnectet Bat(+),Bat(-)    
CNTL NO NEED ANY ADJUSTMENT!

VOLTAGE TYPE ADJUSTMENT

UNINVERAL INPUT VOLTAGE TYPE AND UNIVERAL OUTPUT ADJUST.Its position see FIG -

 

 